WDG-3A - प्रप्लशन कंट्रोल सर्किट ( Propulsion Control Circuit )

 Propulsion Control Circuit 

To move the locomotive, supply of Traction Alternator is send to traction motor through Power contactor, BKT, Reverser. This circuit is design to pickup above electro pneumatic contactor as and when require. In this circuit as per speed of locomotive two combination of traction motor are changed and during dynamic brakes traction motor convert into generator. Traction motor has following combination:

a) Series Parallel combination 
b) Parallel combination 

Reverser Contactor Control – To move the locomotive, keep reverser handle in desired direction, put ON GFCO-1&2 and on opening master handle reverser contactor coil will energize as per working control stand

MH(M)                        NOI 6-13A                  L/C/S 
MH(M)                        NOI 6-13B                  R/C/S 
RH(F)                          NOI 13A-8                  L/C/S 
RH (R)                         NOI 13A-0                  L/C/S 
RH (F)                          NOI 13B-0                  R/C/S 
RH (R)                         NOI 13B-8                   R/C/S 

Rev. Forward coil Wire no. 8& 4 

Rev. reverse coil Wire no. 0 & 4 

Series parallel combination- series power contactors coil will get 


Rev(F)          NCI                             8-8A 
Rev(R)          NOI                             0-8A 
BKR3            NCI                           8A-8C 
BKR1           NCI                           8C-8D
 ECS(Idle)     NOI                           8D-8AA 
BKT(M)         NCI                       8AA-8E 
TR                  NCI                           8E-8F 
GFC                NOI                           8E-8F 
MCO               NOI                      8F-8FF 
P1                  NCI                          8FF – 8M 
S1            Contactor Coil                    8M-4 
P21               NCI                                 8M-8Z 
S21           Contactor Coil                   8Z-4 
P31                NCI                                 8M-8G S31
Contactor     Coil                                 8G-4 

In this way S1, S21, S31 series power contactor pickup. 


Parallel Combination (Ist transition) -When loco speed increases up to 41.5 km/h at that time TSSR energize and its contact 6AA-18A close and TR relay picks up through MCO, NCI 6-6AA and TSSR NOI 6AA-18A, due to which following changes will take place – 

1. TR NCI 6E-6F open and GFC will drop. 

2. TR NCI 8E-8F open and S 1, S21, S31 will drop. 

3. TR NOI 8E-8L close and P1, P21, P31 will pick up through S31 NCI 8L-8S. 

P2, P22, P32 will pick up in following way - 

TR                NOI                     8E-8L 

GFC             NCI                     8L-8R 

BKT (M)      NCI                     8R-8K 

MCO1         NCI                     8K-8KA 

S1                NCI                     8KA-8U 

P2 contactor picks up (8U-4) 

MCO3         NCI                  8K-8KB 

S21             NCI                   8KB-8W 

P22 contactor picks up (8W-4) 

MCO2         NCI                  8K-8KC 
S31              NCI                  8KC-8V
P32 contactor picks up (8V-4) 

As P32, P2 NOI (6D-6F) closes than GFC will pick up. 
As P32 picks up its NOI (8E-8K) will close in parallel to P21, P31 NOI (8E-8K) and P2, P22, P32 supply will maintained. 

In this way all six parallel power contactor pickup. 

Throttle Not Responding to Loco/Load Meter Not Showing Current 


Precaution To Be Taken Before Wedging GFC:- 

1. Ensure that current available in wire no. 6 (If BKT are change its position from braking to motoring it means current is available in wire no.6) 

2. Ensure that cranking contactors are in open condition. 

3. Ensure that BKT is in motoring position. 

Precaution To Be Taken After Wedging GFC:- 

1. First notch current will be excess, so in order to avoid the jerk on the Loco, First open the MH then release loco brakes. 

2. Parallel transition will not come, take manual transition. 

3. Whenever GR/GFOLR operate bring throttle to idle immediately. 

4. Do not use dynamic brakes.







.

Disclaimer: The Information/News/Video provided in this Platform has been collected from different sources. We Believe that “Knowledge Is Power” and our aim is to create general awareness among people and make them powerful through easily accessible Information. NOTE: We do not take any responsibility of authenticity of Information/News/Videos.